The key is calculating control-wire loading from each driver’s 0.1–0.5 mA input. Add the maximum current, not the typical value. Forty drivers therefore require up to 20 mA. If the dimming controller supports 30 mA, only 10 mA remains. That margin is useful, but not generous.
Check the driver datasheet before wiring. Some inputs sink current, while some controllers source it. Polarity also matters. NEMA LSD 49-2019 describes the 0–10V control interface, including its low-voltage signaling practice. A 100-meter cable run can still deserve attention. With 24 AWG copper, an estimated 16.8-ohm loop resistance causes about 0.34V drop at 20 mA. The dimming range may shift slightly. Long runs are rarely perfect.
Use a simple worksheet. Record fixture quantity, maximum input current, controller capacity, cable length, and voltage drop. For 60 drivers, the worst case reaches 30 mA. A 30 mA controller has no practical reserve. Choose a higher-capacity interface or divide the circuit. The U.S. Department of Energy’s 2020 Solid-State Lighting Energy Savings Forecast projected up to 6.2 quads of annual lighting-energy savings by 2035. Reliable controls help achieve that potential. I still verify measurements onsite. Published current values can vary between production batches. A tidy calculation can mislead. Measure the control voltage at the farthest panel, especially when lights flicker, stop below full output, or never reach minimum dimming.